PSL Flamefighter Standards & Compliance

Flamefighter III Ratings & Specification Chart

Compare the upgraded fire ratings, test performance, and specifications between Flamefighter III and the legacy Flamefighter II series. All Flamefighter III models are fully certified to AS/NZS 1841 standards.

Extinguisher Details Flamefighter III Series (Current) Flamefighter II Series (Legacy) Rating Comparison
Extinguisher Size & Type Technical Specs Part No. / SKU Fire Rating Legacy SKU Legacy Rating Upgrade Impact
Dry Powder Extinguishers (ABE) AS/NZS 1841.5 Certified
1.0kg ABE Dry Powder
Compact / Vehicles & Domestic
1.85kg gross • 9s discharge
18425 2A:10B:E 8425 1A:20B:E ↑ 2A Class A rating
1.5kg ABE Dry Powder
Small Vehicles, Vans & Boats
2.84kg gross • 13s discharge
18411 3A:20B:E 8411 2A:20B:E ↑ 3A Class A rating
2.0kg ABE Dry Powder
Commercial Transport & Trucks
3.49kg gross • 16s discharge
18412 3A:30B:E 8412 3A:30B:E Matched Rating
2.5kg ABE Dry Powder
Workshops & Light Commercial
4.53kg gross • 18s discharge
18413 4A:40B:E 8413 3A:40B:E ↑ 4A Class A rating
4.5kg ABE Dry Powder
Commercial, Industrial & Plant
7.36kg gross • 24s discharge
18414 10A:60B:E 8414 4A:60B:E ↑ 10A (+150% Class A)
9.0kg ABE Dry Powder
Heavy Industrial, Warehouses & Fuel
13.76kg gross • 29s discharge
18416 10A:80B:E 8416 6A:80B:E ↑ 10A (+66% Class A)
Carbon Dioxide Extinguishers (CO2) AS/NZS 1841.6 Certified
2.0kg CO2 Extinguisher
Server Rooms, Offices & Switchboards
5.18kg gross • 8s discharge
18465 2B:E 8465 2B:E Matched Rating
3.5kg CO2 Extinguisher
Electrical Substations & Laboratories
9.27kg gross • 11s discharge
18466 10B:E 8466 10B:E Matched Rating
5.0kg CO2 Extinguisher
Industrial Switchgear & Data Centers
12.16kg gross • 13s discharge
18467 10B:E 8467 10B:E Matched Rating
Water & Foam Extinguishers AS/NZS 1841.2 / 1841.4
9.0 Litre Water
Timber, Paper, Textiles (Class A Only)
12.58kg gross • 70s discharge
18485 3A 8485 3A Matched Rating
9.0 Litre Fluorine Free Foam
Eco-friendly / Replaces Legacy AFFF
12.88kg gross • 45s discharge
18495 4A:20B:3F
Fluorine-Free Eco Formula
8490 3A:30B
Legacy AFFF Discontinued
↑ 4A & added 3F capability
Wet Chemical Extinguishers (Commercial Kitchens & Deep Fat Fryers) AS/NZS 1841.3 Certified
2.0 Litre Wet Chemical
Commercial Kitchens, Cafes & Food Trucks
4.33kg gross • 14.5s discharge
18450 1A:4F 8450 1A:4F Matched Rating
7.0 Litre Wet Chemical
High Volume Fryers, Hotels & Restaurants
10.26kg gross • 60s discharge
18455 3A:4F 8455 3A:4F Matched Rating

How To Read Fire Ratings

Under AS/NZS 1850, numbers represent extinguishing capacity and letters designate the fuel fire classification:

  • Numbers (e.g. 10A, 60B): Higher numbers signify a larger test fire extinguished under standardized testing.
  • Class E (Electrical): Indicates electrical non-conductivity safely tested up to 100,000V.
  • Class F (Cooking): Tested against ignited vegetable oil/animal fat deep fryers.

Fluorine-Free Transition

New Zealand and global regulations mandate the phase-out of fluorinated firefighting foams (PFAS/AFFF):

  • Legacy AFFF SKU 8490 is discontinued.
  • The new Flamefighter III 9L Foam (SKU 18495) features 100% fluorine-free bio-degradable foam.
  • Achieves a high 4A:20B:3F rating without toxic environmental persistent chemicals.

Discharge Times & Standards

All Flamefighter III cylinders exceed the minimum discharge duration defined by AS/NZS 1841:

  • Hydrostatic Testing: 2.8 MPa proof pressure on Dry Powder cylinders; 25.0 MPa on CO2 cylinders.
  • Extended Reach: High flow brass valves allow users to fight blazes from safe stand-off distances.
  • Full traceability and manufacturing batch serial numbers stamped on every unit.

Need Help Sizing Extinguishers For Your Site?

Whether you're specifying fire protection for a commercial fit-out, heavy vehicle fleet, or compliance audit, PSL Fire & Safety's technical team can provide tailored recommendations.